Free Sample
Please ask for free sample in order to check if the products meets your requirement for your application.
Send your delivery adress and your specific requirements.
14 Variants
Ratings IEC
0.5 - 6,5 A @ Ta 40 °C / 250 VAC; 50 Hz
Ratings UL/CSA
0.5 - 6.5 A @ Ta 40 °C / 125 VAC; 60 Hz
Leakage Current
standard < 0.25 mA (250 V / 60 Hz)
medical < 5 µA (250 V / 60 Hz)
Dielectric Strength
> 1.7 kVDC between L-N
> 2.7 kVDC between L/N-PE
Test voltage (2 sec)
Allowable Operation Temperature
-25 °C to 85 °C
Climatic Category
25/085/21 acc. to IEC 60068-1
Protection Class
Suitable for appliances with protection class I acc. to IEC 61140
Terminal
For PCB mounting , tin-plated
Material
Thermoplastic, black, UL 94V-0
Line Filter
Standard and Medical Version, IEC 60939, UL 1283, CSA C22.2 no. 8
Technical Details
MTBF
> 200'000 h acc. to MIL-HB-217 F
Rated Current [A] | Filter-Type | L [mH] |
Order Number
|
Free Sample Free Sample
|
Distributor Stock Check Distributor Stock Check
|
... | |
---|---|---|---|---|---|---|---|
0.8 | Standard version | 2 x 20 | 5500.2020 | ... | |||
0.5 | Standard version | 2 x 40 | 5500.2014 | ... | |||
1 | Standard version | 2 x 10 | 5500.2015 | ... | |||
1.6 | Standard version | 2 x 6 | 5500.2016 | ... | |||
2.5 | Standard version | 2 x 2 | 5500.2017 | ... | |||
4 | Standard version | 2 x 1 | 5500.2018 | ... | |||
6,5 | Standard version | 2 x 1 | 5500.2019 | ... | |||
0.8 | Medical Version (M5) | 2 x 20 | 5500.2129 | ... | |||
0.5 | Medical Version (M5) | 2 x 40 | 5500.2127 | ... | |||
1 | Medical Version (M5) | 2 x 10 | 5500.2130 | ... | |||
1.6 | Medical Version (M5) | 2 x 6 | 5500.2131 | ... | |||
2.5 | Medical Version (M5) | 2 x 2 | 5500.2132 | ... | |||
4 | Medical Version (M5) | 2 x 1 | 5500.2133 | ... | |||
6,5 | Medical Version (M5) | 2 x 1 | 5500.2128 | ... |
Packaging unit | 70 Pcs |